i-ZONE 5 Control Panel

i-ZONE 5 Control Panel

The i-Zone Control Panel shall be wall mounted and be of a mild steel construction and powder coated.  It will be capable of monitoring the full range of Aqualarm detectors for water, fuel oils, chemicals, temperature, humidity and refrigerant gases.  The control panel is an addressable system capable of monitoring 5 detectors/addresses simultaneously.

The default detector identification is “Zone 1”, “Zone 2” etc, however these can be programmed to display customer requirements, up to 24 characters per zone i.e. “Zone 1 – Room 5 2nd Floor”.  This has to be carried out at the time of manufacturing.

The control panel can store a 100-alarm event history log into non-volatile memory.  During normal operation, the green LCD screen will display the current time and date together with SYSTEM CLEAR status.

The i-Zone 5 Control Panel can also be linked to a maximum of 5 ZLM-500 modules, resulting in a single system, monitoring between 2500 metres of detecting cable, and in the condition of an alarm, will display a meterage reading accurate to +/- 1 metre to the point of water contact with cable.

The control panel will be provided with a TEST button, MUTE button and the facility to view the 100-event history log.  In an alarm state, the LCD will display the activated detector identification and a 97db (at 1 metre) audible alarm will sound.

For remote signalling, the control panel will be supplied as standard with the following outputs: RS-485, Common Alarm, Network Failure, Mains Fail, Battery Fail and Service Required.

For safety, the control panel is fitted with a key operated door lock and “power off” door switch.

i-ZONE 10/25 Control Panel

i-ZONE 10/25 Control Panel

The i-Zone Control Panel shall be wall mounted and be of a mild steel construction and powder coated.  It will be capable of monitoring the full range of Aqualarm detectors for water, fuel oils, chemicals, temperature, humidity and refrigerant gases.  The control panel is an addressable system capable of monitoring 10-25 detectors/addresses simultaneously.

The default detector identification is “Zone 1”, “Zone 2” etc, however these can be programmed to display customer requirements, up to 24 characters per zone i.e. “Zone 1 – Room 5 2nd Floor”.  This has to be carried out at the time of manufacturing.

The control panel can store a 100-alarm event history log into non-volatile memory.  During normal operation, the blue LCD screen will display the current time and date together with SYSTEM CLEAR status.

The i-Zone 10-25 Control Panel can also be linked to a maximum of 10-25 ZLM-500 modules, resulting in a single system, monitoring between 5000 and 12500 metres of detecting cable, and in the condition of an alarm, will display a meterage reading accurate to +/- 1 metre to the point of water contact with cable.

The control panel will be provided with a TEST button, MUTE button and the facility to view the 100-event history log.  In an alarm state, the LCD will display the activated detector identification and a 97db (at 1 metre) audible alarm will sound.

For remote signalling, the control panel will be supplied as standard with the following outputs: RS-485, Common Alarm, Network Failure, Mains Fail, Battery Fail and Service Required.
For safety, the control panel is fitted with a key operated door lock and “power off” door switch.

Zoned Locating Module Model ZLM-500

Zoned Locating Module Model ZLM-500

The Aqualarm Zoned Locating Module shall be wall mounted and be of a mild steel construction, painted and stove enamelled.

The Zoned Locating Module shall generate Pulsed Echo Radar signals, which shall be transmitted along the entire length of the Leader / Jumper and Detecting Cables. Any change in the characteristics of the cable, whether water detected or open circuit, occurs, these are compared to pre-programmed limits and when these limits are exceeded, an alarm signal providing the meterage reading accurate to +/-1 metre, will be sent to the designated Aqualarm master control panel.

The ZLM-500 is capable of monitoring up to 500m of combined Leader / Jumper and Detection cables.
Power to the ZLM-500 is generated via the Aqualarm CAN network.

A local, volt free alarm contact is available within the ZLM-500. Other alarm contacts will be available from the designated ‘Aqualarm’ master control panel.

The ZLM-500 can only be used within a network-designed system connected to either an i-Zone control panel or One Touch system to monitor and display the relevant alarms and information.